Breaking Capacity: | 25ka, 30ka, 31.5ka, 35ka |
---|---|
Operation: | Manual Type |
Speed: | Normal Type Circuit Breaker |
Arc-extinguishing Medium: | Vacuum |
Installation: | Fixed |
Structure: | ACB |
Customization: |
---|
Suppliers with verified business licenses
Project
|
|
Unit
|
Parameter
|
|
|
|||
Rated voltage
|
|
kV
|
24
|
36
|
40.5
|
|||
Rated insulation level
|
Lightning impulse withstand
|
kV
|
150
|
170
|
210*/215(fracture)185
|
|||
|
voltage (full wave peak)
|
|
|
|
|
|||
|
Power frequency withstand
|
kV
|
65
|
75
|
95
|
|||
|
voltage (1 minute)
|
|
|
|
|
|||
Rated current
|
|
A
|
1250/1600/2000/2500
|
|
|
|||
Mechanical life
|
|
time
|
10000
|
|
|
|||
SF6 gas rated pressure (25 gauge pressure)
|
|
MPa
|
0.45
|
|
|
|||
Blocking pressure (time gauge pressure)
|
|
Mpa
|
0.4
|
|
|
|||
Maximum 4 ºC ambient temperature
|
|
ºC
|
-30
|
|
|
|||
Rated short circuit breaking current
|
|
kA
|
20/25/31.5/40
|
|
|
|||
Rated short circuit making current (peak value)
|
|
kA
|
50/63/80/100
|
|
|
|||
Rated short time withstand current (thermal stability current)
|
|
kA
|
20/25/31.5/40
|
|
|
|||
Rated peak withstand current (dynamic stability current)
|
|
kA
|
50/63/80/100
|
|
|
|||
Rated out of step breaking current
|
|
kA
|
50/63/80/100
|
|
|
|||
Rated short circuit duration
|
|
s
|
4
|
|
|
|||
Closing time (at rated operating voltage)
|
|
ms
|
≤80
|
≤80
|
≤100
|
|||
Opening time (under rated operating voltage)
|
|
ms
|
≤65
|
≤65
|
≤70
|
|||
Rated operating sequence
|
|
|
0-0.3s-CO-180s-CO
|
|
|
|||
Rated switching current of single capacitor bank
|
|
A
|
400
|
|
|
|||
Annual air leakage rate
|
|
%/year
|
≤1
|
|
|
|||
Water content of SF6 gas (at 20 ºC)
|
|
PPm(V/V)
|
≤150
|
|
|
|||
Rated operating voltage of ct14 spring operating mechanism
|
|
V
|
DC:110,220 AC; 110, 220,380
|
|
|
|||
Closing coil and breaking coil voltage
|
|
V
|
DC:110,220 AC; 110, 220,380
|
|
|
|||
Voltage of energy storage motor
|
|
V
|
AC:220 DC:220
|
|
|
|||
Closing speed
|
|
m/s
|
3.2 ± 0.2
|
3.2 ± 0.2
|
3.2 ± 0.2
|
|||
Opening speed
|
|
m/s
|
3.4±0.2
|
3.4±0.2
|
3.4±0.2
|
|||
Weight of sulfur hexafluoride gas
|
|
kg
|
7-8
|
|
|
|||
Weight of circuit breaker (including operating mechanism)
|
|
kg
|
800/900/1400
|
|
|