Breaking Capacity: | 25ka, 31.5ka, 35ka, 36ka, 40ka |
---|---|
Operation: | Manual Type |
Speed: | Normal Type Circuit Breaker |
Arc-extinguishing Medium: | Vacuum |
Installation: | Fixed |
Structure: | ACB |
Customization: |
---|
Suppliers with verified business licenses
Environmental conditions
|
|
|
Installation site
|
outdoor
|
|
Ambient temperature
|
-25ºC~+40ºC
|
|
Max. daily temperature difference
|
≤25ºC
|
|
Height above sea level
|
2000m(no limit for specified order)
|
|
Air humidity
|
Daily average:≤95%;
month average:≤90%; |
|
Wind speed
|
≤34m/s
|
|
Solar radiation
|
≤0.1W/cm2(fine day, noon)
|
|
Earthquake intensity
|
horizontal:≤0.3g;vertical:≤0.15g
|
|
Icing thickness
|
≤10mm
|
|
Creepage distance
|
25mm/kV or 31mm/kV
|
|
Static load on terminal in Y-direction
|
1250N
|
|
Static load on terminal in X-direction
|
750N
|
|
Static load on terminal in Z-direction
|
1000N
|
Main Technical data
|
|
|
|
|
|
|||||
No.
|
Items
|
|
|
Unit
|
Parameter
|
|||||
1
|
Rated voltage
|
|
|
kV
|
126
|
|||||
2
|
Rated power frequency withstand voltage(1min)
|
|
Phase-to-phase
|
kV
|
230
|
|||||
|
|
|
Phase-to-ground
|
|
|
|||||
|
|
|
fracture
|
kV
|
230+73*
|
|||||
3
|
Rated lightning impulse withstand voltage
|
|
Phase-to-phase
|
kV
|
550
|
|||||
|
|
|
Phase-to-ground
|
|
|
|||||
|
|
|
fracture
|
kV
|
550+103*
|
|||||
4
|
Power frequency withstand voltage(5min)under SF6 zero-gauge pressure
|
|
|
kV
|
95
|
|||||
5
|
Rated frequency
|
|
|
Hz
|
50
|
|||||
6
|
Rated current
|
|
|
A
|
3150
|
|||||
7
|
Rated short circuit breaking current
|
|
|
kA
|
40
|
|||||
8
|
First-pole-to-clear factor
|
|
|
|
1.5
|
|||||
9
|
Rated short circuit breaking current
|
|
|
|
More than 41%
|
|||||
|
(DC component)
|
|
|
|
|
|||||
10
|
Rated short circuit making current (peak)
|
|
|
kA
|
100
|
|||||
11
|
Rated short time withstand current(rms)
|
|
|
kA
|
40
|
|||||
12
|
Rated peak withstand current
|
|
|
kA
|
100
|
|||||
13
|
Rated short circuit duration
|
|
|
s
|
4
|
|||||
14
|
Rated out-of-phase breaking current
|
|
|
kA
|
3(OP1) ,10(OP2)
|
|||||
15
|
Short range breaking current
|
|
|
kA
|
36;30
|
|||||
16
|
Wrong-phase earthing fault
|
|
|
kA
|
34.8
|
|||||
|
breaking current
|
|
|
|
|
|||||
17
|
Rated line charging switching current
|
|
|
A
|
31.5
|
|||||
18
|
Full capacity breaking time without check and repair
|
|
|
Times
|
20 or rated current breaking times:3000
|
|||||
19
|
Rated operating sequence
|
|
|
|
O-0.3s-CO-180s-CO
|
|||||
20
|
Rated SF6 pressure (20ºC gauge)
|
|
|
MPa
|
0.6
|
|||||
21
|
Alarm/Lock pressure(20ºC gauge)
|
|
|
MPa
|
0.55/0.50
|
|||||
22
|
SF6 annual leakage rate
|
|
|
%/Y
|
≯0.5
|
|||||
23
|
Gas moisture content
|
Check value
|
|
μL/L
|
≯150
|
|||||
|
|
after hand over
|
|
|
|
|||||
|
|
Allowed service
|
|
μL/L
|
≯300
|
|||||
|
|
value
|
|
|
|
|||||
24
|
Resistance of the main circuit
|
|
|
μΩ
|
≤35
|
|||||
25
|
Mechanical life
|
|
|
Time
|
6000
|
|||||
26
|
Radio interference level (1.1Ur/)
|
|
|
μV
|
≯500
|
|||||
27
|
Allowed partial discharge intensity(1.2Ur)
|
|
|
pC
|
≤5
|
|||||
28
|
Noise(distance from sound source:horizontality:2m,height:1.5m)
|
|
|
dB
|
90
|