Technical Sheet:
(It can be customized according to customer's local demand!)
S13-M.RL Type 6~10kV
Rated capacity (KVA) |
Voltage Combination and tap range |
Connection of transformer winding |
No-load loss (w) |
Load loss (W) |
No-load current (%) |
Short circuit impedance (%) |
||
High voltage (KV) |
High voltage tap range (%) |
Low voltage (KV) |
||||||
30 50 63 80 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 |
6 6.3 6.6 10 10.5 11 |
±5% ±2x2.5% |
0.4 |
Dyn11 Yzn11 Yyn0 |
80 100 110 130 150 170 200 240 290 340 410 480 570 700 830 970 1170 |
630/600 910/870 1090/1040 1310/1250 1580/1500 1890/1800 2310/2200 2730/2600 3200/3050 3830/3650 4520/4300 5410/5150 6200 7500 10300 12000 14500 |
0.3 0.24 0.23 0.22 0.21 0.2 0.19 0.18 0.17 0.16 0.16 0.16 0.15 0.15 0.14 0.13 0.12 |
4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.5 4.5 4.5 4.5 4.5 |
Altitude: ≤ 2000m.
Temperature range: -5 °C to +40 °C, and the average temperature within 24 hours should not exceed +35 °C.
The relative humidity should not exceed 50% at +40 °C, and higher relative humidity is allowed at low temperature (90% at +20 °C). And air must be clean.
Workplaces should be free of fire, explosion, serious pollution, chemical corrosion and severe vibration.
Gradient: ≤ 5°, vertical installation.
Temperature range of transportation & storage: -25 °C to +55°C, and the temperature can be up to +70 °C in short time (within 24 hours).
Product Introduction:
The S11-M fully sealed distribution transformer uses high-qualityhigh magnetic orientation silicon steel sheets as its iron core. Afteroptimization design, the no-load loss is reduced by about 30% onaverage compared to the Sll type.lt is currently a new energy-savingproduct second only to the S (B) H15 type amorphous alloy trans-former and has a high cost-effectiveness. Suitable for power plants(stations),substations (distribution stations), as well as industrial,commercial, construction and other fields.lmplement national stan.dards such as GB1094 and GB20052
working conditions:
GB1094.1-2013 Power Transformers Part 1G1094.2-2013 Power Transformers Part 2GB1094.3-2003 Power Transformers Part 3
GB/1094.5-2008 Power Transformers Part 5
GB/T6451-2015 Technical parameters and requirements for three-phase oilimmersed power transformers
GB/T25289-2010Technical parameters and requirements for 20K\oil immersed distribution transformers International
Standard lEC76
We have established a sound quality management system, and have passed the certification of ISO9001:2015 quality management system, ISO14001:2015 environmental management system, and ISO45001:2018 occupational health and safety management system.
Note:
The following technical information should be provided when placing an order: Main wiring scheme number, purpose and single line system diagram, rated voltage and rated current rated short-circuit breaking current/distribution room layout plan and arrangement and configuration diagram of switchgear;
Requirements for control measurement and protection functions of switchgear, as well as requirements and schematic diagrams for other interlocking and automatic devices;
The models specifications and quantities of the main electrical components inside the switchgear;
When the switchgear is used in special environmental conditions; detailed instructions should be provided when placing an order;