Customization: | Available |
---|---|
Breaking Capacity: | 20ka, 25ka, 31.5ka |
Operation: | Manual Type |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
No. | Item | Unit | Data |
1 | Rated voltage | kV | 24 |
2 | Rated Current | A | 630/1250/1600/2000/2500/3150 |
3 | Rated Frequency | Hz | 50/60 |
4 | Rated short circuit current | kA | 20/25/31.5/40 |
5 | Rated short time withstand current(4s) | kA | 20/25/31.5/40 |
6 | Rated peak withstand current | kA | 50/63/80/100 |
7 | Rated power frequency withstand voltage | kV | 65 (fracture 79) |
8 | Rated lightning impluse withstand voltage | kV | 125(fracture 145) |
9 | Rated operating sequence | O-0.3S-C&O-180S-C&O | |
10 | Mechanical life endurance | time | 10000 |
11 | Rated short circuit opening current frequancy | time | 50 |
12 | Rated voltage of operating mechanism(DC) | V | 110/220 |
13 | Open contact clerance | mm | 11+1 |
14 | Super stroke | mm | 3.5+0.5 |
15 | Time differential among phases | ms | ≤2 |
16 | Bounce time of closing contacts | ms | ≤2 |
17 | Average opening speed | ms | 1.5+0.2 |
18 | Average closing speed | ms | 0.8+0.2 |
19 | Opening time | ms | ≤50 |
20 | Closing time | ms | ≤100 |
Rated voltage | Rated current | Rated short-circuit | P | A | B | D |
KV | KA | breaking current, KA | mm | mm | mm | mm |
12 | 630,1250 | 20,25,31.5 | 150 | 20 | 410 | 450 |
Rated voltage | Rated current | Rated short-circuit | P | A | B | C | D | W |
KV | KA | Breaking current, kA | mm | mm | mm | mm | mm | mm |
630 | 20,25 | 35 | ||||||
12 | 630,1250 | 20,25,31.5,40 | 150 | 494 | 456 | 490 | 502 | 49 |
Series Number | Symbol | Name | Remark |
1 | YQ-Y9 | Indirect over-current release | Chosen element |
2 | Y1-Y4 | Rectifier element | |
3 | KO | Inner mechanism anti-jumping relay | |
4 | P | Handle operation mechanism | |
5 | Y1 | blocking eletromagnet | Chosen element |
6 | HQ | Closing release | |
7 | TQ | Breaking release | |
8 | M | Energy storing engine | |
9 | S9 | assistant switch used at operation position | |
10 | S8 | assistant switch used, at test positin | Chosen element |
11 | S2 | Blocking electromagnet assistant switch | |
12 | S1 | Inching switch for energy storing | |
13 | QF | assistant switch of breaker contact |