Customization: | Available |
---|---|
Breaking Capacity: | 20ka, 25ka, 31.5ka |
Operation: | Manual Type |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
VS1-24 series solid-sealed indoor vacuum circuit breaker is a three-phase power system indoor high-voltage switchgear with a rated voltage of 24kV and a frequency of 50Hz. Because of the vacuum circuit breaker, it is used to protect and control electrical appliances. Special advantages are particularly suitable for frequent operation requiring rated current or multiple short-circuit currents.
VS1-24 series solid-sealed indoor vacuum circuit breaker is a fixed installation, mainly used for fixed switchgear. The circuit breaker can be used alone, or used for ring network power supply, box transformer or various non-power supply systems.
(It can be customized according to customer's local demand!)
Item |
Unit |
Parameter |
|||
Rated voltage |
KV |
12 |
|||
Max. operating voltage |
KV |
12 |
|||
Rated current |
A |
630/1250 |
630/1250 |
630/1250 |
|
Rated short circuit breaking current |
KA |
20 |
25 |
31.5 |
|
Rated short current switching current |
KA |
50 |
63 |
80 |
|
Rated peak withstand current |
KA |
50 |
63 |
80 |
|
Rated short time withstand current |
KA |
20 |
25 |
31.5 |
|
Rated insul-ation level |
Power frequency withstand voltage |
Kv |
42 (Fracture 48) |
||
Impulse withstand voltage |
75 (Fracture 84) |
||||
Rated operating sequence |
|
O-0.3s-CO-180s-CO |
|||
Mechanical life |
times |
20000 |
|||
Rated frequency |
Hz |
50 |
|||
Operating mechanism rated switch-on voltage (DC) |
V |
110, 220 |
|||
Operating mechanism rated off voltage (DC) |
V |
110, 220 |
|||
Contact opening |
mm |
11±1 |
|||
Overtravel (Compressed length of contact spring) |
mm |
3.5±0.5 |
|||
Three-phase switching on or off non-synchroneity |
ms |
≤2 |
|||
Contact closing bounce time |
ms |
≤2 |
|||
Average Switch off speed |
m/s |
0.9-1.2 |
|||
Average switching on speed |
m/s |
0.4-0.8 |
|||
Switch-off time |
Under max. operation voltage |
s |
≤0.05 |
||
Under min. operation voltage |
≤0.08 |
||||
Switch-on time |
s |
0.1 |
|||
Loop resistance |
uΩ |
60 |
40 |
||
Each phase loop DC resistance |
mm |
3 |
1. The upper limit of ambient air temperature shall not be higher than + 40 ºC, and the lower limit shall not be lower than - 15 ºC (it is allowed to store and transport at - 30 ºC):
2. When the product is used in 7.2kV system in the area with an altitude of no more than 1000m, the applicable altitude can be increased to 3000m;
3. Relative humidity: daily average value is not more than 95%, and monthly average value is not more than 90%;
4. Saturated steam pressure: the daily average value is not more than 2.2 × 103mpa, and the monthly average value is not more than 1.8 × 103mp. When the temperature drops sharply in the humidity period, condensation may occur;
5. The installation site shall be free from frequent violent vibration;
6. The surrounding air shall be free from the obvious pollution of corrosive or combustible gas and water vapor;
7. The installation site shall be dry and clean;
8. The earthquake intensity shall not exceed 8 degrees.
Rated voltage | Rated current | Rated short-circuit | P | A | B | D |
KV | KA | breaking current, KA | mm | mm | mm | mm |
12 | 630,1250 | 20,25,31.5 | 150 | 20 | 410 | 450 |
Rated voltage | Rated current | Rated short-circuit | P | A | B | C | D | W |
KV | KA | Breaking current, kA | mm | mm | mm | mm | mm | mm |
630 | 20,25 | 35 | ||||||
12 | 630,1250 | 20,25,31.5,40 | 150 | 494 | 456 | 490 | 502 | 49 |
Series Number | Symbol | Name | Remark |
1 | YQ-Y9 | Indirect over-current release | Chosen element |
2 | Y1-Y4 | Rectifier element | |
3 | KO | Inner mechanism anti-jumping relay | |
4 | P | Handle operation mechanism | |
5 | Y1 | blocking eletromagnet | Chosen element |
6 | HQ | Closing release | |
7 | TQ | Breaking release | |
8 | M | Energy storing engine | |
9 | S9 | assistant switch used at operation position | |
10 | S8 | assistant switch used, at test positin | Chosen element |
11 | S2 | Blocking electromagnet assistant switch | |
12 | S1 | Inching switch for energy storing | |
13 | QF | assistant switch of breaker contact |