Vs1-24 Fixed Indoor High Voltage Vacuum Circuit Breaker

Breaking Capacity: 20ka, 25ka, 31.5ka
Operation: Manual Type
Speed: Normal Type Circuit Breaker
Arc-extinguishing Medium: Oil-immersed Type
Installation: Fixed
Structure: ACB
Customization:
Manufacturer/Factory

360° Virtual Tour

Diamond Member Since 2023

Suppliers with verified business licenses

Zhejiang, China
Self-branded
The supplier has 2 Self-brands, check the Audit Report for more information
ODM Services
The supplier provides ODM services
OEM Services
The supplier provides OEM services for popular brands
Management Certification
The supplier has quality management system certification, including:
ISO9001:2015 certificate
ISO45001:2018 certificate
ISO14001
to see all verified strength labels (23)
  • Overview
  • Product Description
  • Felds of Application
  • Company Profile
  • Certifications
  • Delivery
  • FAQ
Overview

Basic Info.

Model NO.
VS1-24
Poles Number
1
Type
Circuit Breaker
Function
Conventional Circuit Breaker
Certification
VDE, ISO9001:2008
Product Name
Zw32c-12
Rated Current
630
Application
Electric Power Transmission
MOQ
1 Piece
Rated Voltage
12
Transport Package
Standard
Specification
standard
Trademark
GGAOE
Origin
Zhejiang, China
HS Code
7201500010
Production Capacity
100000 Piece/Pieces Per Month

Product Description

Product Description

 

VS1-24 series solid-sealed indoor vacuum circuit breaker is a three-phase power system indoor high-voltage switchgear with a rated voltage of 24kV and a frequency of 50Hz. Because of the vacuum circuit breaker, it is used to protect and control electrical appliances. Special advantages are particularly suitable for frequent operation requiring rated current or multiple short-circuit currents.

VS1-24 series solid-sealed indoor vacuum circuit breaker is a fixed installation, mainly used for fixed switchgear. The circuit breaker can be used alone, or used for ring network power supply, box transformer or various non-power supply systems.

Technical Sheet:

(It can be customized according to customer's local demand!)

Item

Unit

Parameter

Rated voltage

KV

12

Max. operating voltage

KV

12

Rated current

A

630/1250

630/1250

630/1250

Rated short circuit breaking current

KA

20

25

31.5

Rated short current switching current

KA

50

63

80

Rated peak withstand current

KA

50

63

80

Rated short time withstand current

KA

20

25

31.5

Rated insul-ation level

Power frequency withstand voltage

Kv

42 (Fracture 48)

Impulse withstand voltage

75 (Fracture 84)

Rated operating sequence

 

O-0.3s-CO-180s-CO

Mechanical life

times

20000

Rated frequency

Hz

50

Operating mechanism rated switch-on voltage (DC)

V

110, 220

Operating mechanism rated off voltage (DC)

V

110, 220

Contact opening

mm

11±1

Overtravel (Compressed length of contact spring)

mm

3.5±0.5

Three-phase switching on or off non-synchroneity

ms

≤2

Contact closing bounce time

ms

≤2

Average Switch off speed

m/s

0.9-1.2

Average switching on speed

m/s

0.4-0.8

Switch-off time

Under max. operation voltage

s

≤0.05

Under min. operation voltage

≤0.08

Switch-on time

s

0.1

Loop resistance

60

40

Each phase loop DC resistance

mm

3

 

 

 

Working conditions:

 

1. The upper limit of ambient air temperature shall not be higher than + 40 ºC, and the lower limit shall not be lower than - 15 ºC (it is allowed to store and transport at - 30 ºC):

2. When the product is used in 7.2kV system in the area with an altitude of no more than 1000m, the applicable altitude can be increased to 3000m;

3. Relative humidity: daily average value is not more than 95%, and monthly average value is not more than 90%;

4. Saturated steam pressure: the daily average value is not more than 2.2 × 103mpa, and the monthly average value is not more than 1.8 × 103mp. When the temperature drops sharply in the humidity period, condensation may occur;

5. The installation site shall be free from frequent violent vibration;

6. The surrounding air shall be free from the obvious pollution of corrosive or combustible gas and water vapor;

7. The installation site shall be dry and clean;

8. The earthquake intensity shall not exceed 8 degrees.


Alternative parameters table1
Rated voltage Rated current Rated short-circuit P A B D
KV KA breaking current, KA mm mm mm mm
12 630,1250 20,25,31.5 150 20 410 450
Alternative parameters table2                           
Rated voltage Rated current Rated short-circuit P A B C D W
KV KA Breaking current, kA mm mm mm mm mm mm
  630 20,25           35
12 630,1250 20,25,31.5,40 150 494 456 490 502 49
 
Series Number Symbol Name Remark
1 YQ-Y9 Indirect over-current release Chosen  element
2 Y1-Y4 Rectifier element  
3 KO Inner mechanism anti-jumping relay  
4 P Handle operation mechanism  
5 Y1 blocking eletromagnet Chosen element
6 HQ Closing release  
7 TQ Breaking release  
8 M Energy storing engine  
9 S9 assistant switch used at operation position  
10 S8 assistant switch used, at test positin Chosen element
11 S2 Blocking electromagnet assistant switch  
12 S1 Inching switch for energy storing  
13 QF assistant switch of breaker contact  
 

Ordering Instructions:

The following technical information should be provided when placing an order: Main wiring scheme number, purpose and single line system diagram, rated voltage and rated current rated short-circuit breaking current/distribution room layout plan and arrangement and configuration diagram of switchgear;
Requirements for control measurement and protection functions of switchgear, as well as requirements and schematic diagrams for other interlocking and automatic devices;
The models specifications and quantities of the main electrical components inside the switchgear;
When the switchgear is used in special environmental conditions; detailed instructions should be provided when placing an order;

Felds of Application

Vs1-24 Fixed Indoor High Voltage Vacuum Circuit Breaker
Vs1-24 Fixed Indoor High Voltage Vacuum Circuit Breaker

Company Profile

Vs1-24 Fixed Indoor High Voltage Vacuum Circuit Breaker
Vs1-24 Fixed Indoor High Voltage Vacuum Circuit Breaker

Certifications

Vs1-24 Fixed Indoor High Voltage Vacuum Circuit Breaker

Delivery

Vs1-24 Fixed Indoor High Voltage Vacuum Circuit BreakerVs1-24 Fixed Indoor High Voltage Vacuum Circuit Breaker
 

FAQ

Q:what's your major products?
A: oil immersed transformer, dry type transformer, Transformer Substation, High and Low Voltage Switchgear

Q: Can your product be customized?
A: Considering differences in voltage, frequency and other special transformer product in different countries and regions, our product can be customized according to your requirements.

Q: When can I get the price?
A:Usually we quote within 24 hours after we get your inquiry.

Q: What about lead or shipping time?
A: The lead time depends on the quantity you ordered, generally within 15 days upon receipt of advance payment.

Q: What is the price of shipping?
A: Depending upon the port of delivery, prices varies.

Q: Do you offer guarantee for the products?
A: Yes. We offer at least one years guarantee for all of our transformers.

Q: Your Advantage?
A: 15 years experience, Advanced production equipment, Stable quality, Fast delivery, Professional & good & Prompt service. Also some free parts can be provided for you.

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now