Breaking Capacity: | 25ka, 30ka, 31.5ka |
---|---|
Operation: | Manual Type |
Speed: | Normal Type Circuit Breaker |
Arc-extinguishing Medium: | Vacuum |
Installation: | Fixed |
Structure: | ACB |
Customization: |
---|
Suppliers with verified business licenses
Technical parameter
|
|
|
||
Item
|
Unit
|
Specification
|
||
Rate voltage
|
kV
|
40.5
|
||
Rate current
|
A
|
1250/1600
|
||
Rate frequency
|
Hz
|
50 & 60
|
||
Power frequency withstand voltage (dry) (wet),ground/fracture
|
kV
|
80 95/95
|
||
Lightning impulse withstand current (peak) phase to phase,ground/fracture
|
kV
|
185
|
||
Rated short-circuit breaking current
|
kA
|
25/31.5
|
||
Rated short-circuit making current (peak)
|
kA
|
63/80
|
||
Rated peak withstand current
|
kA
|
63/80
|
||
Short-time withstand current,4S
|
kA
|
25/31.5
|
||
Rated operating cycle
|
|
O-0.1s -CO-3s -CO-6s CO-60s Recover
|
||
Rated short-circuit current breaking times
|
times
|
30
|
||
Mechanical life
|
times
|
10000
|
||
Mechanism control voltage
|
V
|
AC/DC220
|
||
Power frequency withstand voltage of secondary circuit (1min )
|
kV
|
2
|
Item
|
Unit
|
Specification
|
Contact stroke
|
mm
|
16±1
|
Contact over-travel
|
mm
|
4±0.5
|
Opening speed
|
m/s
|
1.4-1.8
|
Closing speed
|
m/s
|
0.4-0.8
|
Contact closing bouncing duration
|
ms
|
≤5
|
Center distance between phases
|
mm
|
460±2
|
Opening/Closing synchronism between poles
|
ms
|
≤2
|
Conductive loop resistance of each phase
|
μΩ
|
< 80
|
Closing time
|
ms
|
≤100
|
Opening time
|
ms
|
≤50
|
Weight
|
Kg
|
270
|
Suppliers with verified business licenses